Teach-in Ultrasonic Sensors.
Teach-in ultrasonic sensors allow various parameters such as range and switching points to be defined by the user. the settings are changed using the indicators and buttons on the sensor end cap. The following series of charts shows how this is done.

P44 Teach-in sensor end cap

Picture of end cap of teach-in ultrasonic sensor

 

The diagram shows the end cap of a PIL P44 Ultrasonic teach-in sensor.
P1 indicates when the first switching point is active
P2 indicates when the second switching point is active.
The key is used to make settings.

P44 Teach-in sensor, teach-in procedure; step 1

Teach in ultrasonic sensors,teach in procedure step 1

In this diagram, the Teach-in sensors is operating and has not detected any object. Switching points P1 and P2 are set as delivered from the factory or previously modified. The analog output is +10V
P44 Teach-in sensor, teach-in procedure; step 2
Teach in ultrasonic sensors,teach in procedure step 2 Normal function of sensor, an object is detected outside the selected switching range (P1 to P2). Output is 10V.
P44 Teach-in sensor, Teach-in procedure; step 3
Teach in ultrasonic sensors,teach in procedure step 3

Normal function of a sensor, an object is detected between the two switching points. Output is 7V indicating the distance from switching point P1

.
P44 Teach-in sensor, Teach-in procedure; step 4
Teach in ultrasonic sensors,teach in procedure step 4

Normal function of a sensor, an object is detected inside switching point P1. Output is 0V indicating relative position of object.

To "teach in" switching point P1 (0V) press key for approx 8sec until both echo LED and P1 LED are blinking
Release key, echo LED blinks when object is detected, P1 LED is blinking.

P44 Teach-in sensor, Teach-in procedure; step 5
Teach in ultrasonic sensors,teach in procedure step 5

To "teach in" a new position for P1, move the object to the new position.

The echo LED indicates that the object is detected, output is 0V

The echo LED is blinking

P44 Teach-in sensor, Teach-in procedure; step 6
Teach in ultrasonic sensors,teach in procedure step 6

Press and release the key; if the echo LED is on when the key is pressed the sensor has NO (normally open) characteristics; if LED is off the sensor is NC (normally closed).

P1 is set in a new position, output is 0V

P44 Teach-in sensor, Teach-in procedure; step 7
Teach in ultrasonic sensors,teach in procedure step 7 To set a new position for P2, press the key until the echo LED and P2 LED are blinking.
P44 Teach-in sensor, Teach-in procedure; step 8
Teach in ultrasonic sensors,teach in procedure step 8

Move the object to a new (10V) position for P2.The echo LED and P2 LED are still blinking. Output is 10V.

P44 Teach-in sensor, Teach-in procedure; step 9
Teach in ultrasonic sensors,teach in procedure step 9

With the object in the new position for P2, press and release the key.

The sensor is "teached in" the new position for P2 output is 10V